Powerware 9125 Rack Mounted 700-6000 Volt Amps *Time: 5 / 16 min (full / half load)
Combining superior backup power management and performance with innovative features, the Powerware 9125 UPS delivers the ultimate in power quality.
Models
- Powerware 9125-700 VA
- Powerware 9125-1000 VA
- Powerware 9125-1250 VA
- Powerware 9125-2000 VA
- Powerware 9125-2500 VA
- Powerware 9125-3000 VA
- Powerware 9125-5000 VA
- Powerware 9125-6000 VA
Features
- Incorporates both a rectifier and inverter to completely isolate the output power from all nine input anomalies, including outages, sags, surges, spikes, brownouts, line noise, frequency variation, switching transients, and harmonic distortion
- Increases battery life (compared to trickle-charged systems) and optimizes battery recharge time through Advanced Battery Management (ABM)® technology) resulting in more up-time and fewer battery replacements
- Double-conversion online design constantly conditions and controls AC output to assure a zero delay transferring to backup power in the event of an utility power failure
- Maximizes battery backup time for critical systems with the ability to independently control Load Segments, enabling you to manage scheduled shutdowns and sequential startups of protected loads
- Enables users to remotely reboot locked-up network equipment, using the Load segments (feature with Powerware ConnectUPS connectivity cards (700-3000 VA units)
- Accepts up to four "hot-swappable" Extended Battery Modules (EBMs) to provide additional battery backup capacity as necessary, without interrupting UPS operation and load protection
- Provides up to 3000 VA of UPS power in only two units (2U) of rack space; up to 6000 VA in 5U, to conserve valuable rack space, with tower pedestal kits, optional rack kits, and seismic kits available
- Ensures data and system integrity with LanSafeT power management software that uses an intuitive, graphical interface and SNMP (Simple Network Management Protocol) to provide control and visibility over multiple UPS products
- Offers a standard RS-232 serial communications port and connectivity options available to suit any communication requirement for remote monitoring
- Offers optional PowerPass® power distribution modules that include a maintenance bypass switch to upgrade or replace the UPS without interrupting power
- Ensures data integrity with free Software Suite bundle including LanSafeT software, PowerVision® software, and NetWatch
- Selected models available in black
Combining superior backup power and power quality management with innovative features, the Powerware 9125 Rackmount UPS delivers the ultimate in power protection. This compact rackmount UPS protects critical applications from downtime, data loss and corruption, and process interruption by providing continuous, conditioned power to all connected equipment.
Offering much more than a surge protector, the Powerware 9125 Rackmount UPS delivers power quality protection against the full range of power anomalies - making power-related downtime a thing of the past. A double-conversion online system, the Powerware 9125 Rackmount UPS is constantly conditioning AC output, and in the event of an outage, it transfers to backup power with zero delay. A "load segments" feature enables orderly shutdown of non-critical systems to extend battery backup power time available for critical systems.
Advanced Battery Management (ABM)® technology
The lead-acid batteries typically used in a UPS are considered viable as long as they can maintain backup times of at least half that of new batteries. Virtually all other UPSs on the market today have batteries that are constantly trickle charged. Those batteries reach the end of their useful life in less than half the time of batteries that are charged using ABM. ABM uses a three-stage charging technique that not only doubles battery service life, but also optimizes battery recharge time and provides up to a 60-day advanced notification of the end of useful battery life.
Extended Battery Modules (EBMs)
Load Segments are groups of receptacles that can be independently controlled via LanSafeT/FailSafeT power management software, which is bundled with the UPS. Load Segments extend battery backup times for critical equipment.
Load segments
Load Segments are groups of receptacles that can be independently controlled via LanSafeT/FailSafeT power management software, which is bundled with the UPS. Load Segments extend battery backup times for critical equipment.
Run Times
700-1000 VA Models
| Load |
Standard Internal Batteries |
+1 EBM |
+2 EBM |
| 200 VA/140 W |
37 min |
271 min |
546 min |
| 400 VA/280 W |
19 min |
142 min |
278 min |
| 700 VA/490 W |
9 min |
72 min |
156 min |
| 850 VA/595 W |
6 min |
59 min |
124 min |
| 1250 VA/875 W |
11 min |
46 min |
87 min |
| 1000 VA/700 W |
5 min |
48 min |
104 min |
1250-2000 VA Models
| Load |
Standard Internal Batteries |
+1 EBM |
+2 EBM |
+3 EBM |
+4 EBM |
| 400 VA/280 W |
46 min |
177 min |
331 min |
501 min |
682 min |
| 700 VA/490 W |
25 min |
96 min |
180 min |
272 min |
370 min |
| 850 VA/595 W |
21 min |
76 min |
142 min |
214 min |
292 min |
| 1000 VA/700 W |
16 min |
61 min |
115 min |
174 min |
237 min |
| 1250 VA/875 W |
11 min |
46 min |
87 min |
131 min |
179 min |
| 1500 VA/1050 W |
8 min |
37 min |
70 min |
106 min |
144 min |
| 1800 VA/1260 W |
6 min |
30 min |
57 min |
85 min |
116 min |
| 2000 VA/1400 W |
5 min |
26 min |
49 min |
74 min |
100 min |
2500-3000 VA Models
| Load |
Standard Internal Batteries |
+1 EBM |
+2 EBM |
+3 EBM |
+4 EBM |
| 1250 VA/875 W |
16 min |
57 min |
90 min |
150 min |
200 min |
| 1500 VA/1050 W |
13 min |
55 min |
72 min |
120 min |
160 min |
| 2500 VA/1750 W |
7 min |
28 min |
48 min |
68 min |
88 min |
| 3000 VA/2100 W |
5 min |
25 min |
38 min |
54 min |
70 min |
5000-6000 VA Models
| Load |
Standard Internal Batteries |
+1 EBM |
+2 EBM |
+3 EBM |
+4 EBM |
| 1000 VA/700 W |
64 min |
179 min |
308 min |
448 min |
na |
| 2000 VA/1400 W |
38 min |
108 min |
186 min |
271 min |
362 min |
| 3000 VA/2100 W |
34 min |
70 min |
122 min |
178 min |
237 min |
| 4000 VA/2800 W |
19 min |
49 min |
86 min |
125 min |
168 min |
| 5000 VA/3500 W |
13 min |
37 min |
65 min |
96 min |
128 min |
| 6000 VA/4200 W |
10 min |
30 min |
52 min |
76 min |
102 min |
|